MSA Chillgard 5000

MSA Chillgard® 5000 Refrigerant Leak Monitor

SKU
FGFD0002 -1

The Chillgard 5000 Refrigerant Leak Monitor enables the earliest possible detection of costly refrigerant leaks in engine rooms. The sampling system with the patented photoacoustic infrared technology (PAIR) detects leaks down to 1 ppm (parts per million). The intuitive touchscreen user interface makes operation easy. Predictive maintenance and diagnostics keep you up and running.

Downloads

Details

The Chillgard 5000 Refrigerant Leak Monitor provides the earliest level of detection of expensive refrigerant gas leaks in mechanical equipment rooms. Sampling system with patented Photoacoustic Infrared (PAIR) technology detects leaks as low as 1 part per million (ppm). Intuitive, touchscreen user interface makes it easy to operate. Predictive maintenance and diagnostics keep you operational.

This product is available in several options and the price is therefore on request. For more information and pricing, please contact us at info@msasafetyshop.com .

Specifications

Meets ASHRAE 15 requirements to provide visual and audible alarms both inside and outside mechanical equipment spaces and to activate mechanical ventilation.

  • Sensitivity - earliest detection level down to 1 ppm
  • Reliability - advanced sensor diagnostics and predictive maintenance
  • Versatility - monitors up to 6 refrigerant field selectable via a refrigerant library
  • Stability - minimal drift, unaffected by temperature or humidity

Intuitive, multilingual user interface puts valuable data at your fingertips:

  • Real-time dashboard view
  • < li>One touch calibration
  • Event logs
  • Password protected

Digital communication:

  • BACnet®
  • Modbus

General Information

More Information

More Information
AC POWER 100–240 Vac, 50/60 Hz, 200VA
Operating temperature 32° to 122° F (0° to 50° C)
Operating humidity 0 to 95%, noncondensing
Ingress Protection IP54
Sensor Type Photoacoustic Infrared (PAIR)
Measuring range 0 – 1000 ppm
Sensitivity 1 ppm for all refrigerant gases
Sensor response time 90% of gas reading <70 sec
Audible alarm 95 ±5 dB(A) at 61 cm